Models
|
80K
|
100K
|
125K
|
|
Input DC (PV side)
|
|||
|
Recommended max. PV array size
|
160 kW
|
200 kW
|
240 kW
|
|
Max. usable PV input power
|
160 kW
|
200 kW
|
240 kW
|
|
Max. input voltage
|
1000 V
|
||
|
MPPT voltage range
|
150 - 950 V
|
||
|
MPPT number / Max. input strings number
|
10 / 20
|
||
|
Battery
|
|||
|
Battery type
|
Li-ion
|
||
|
Battery voltage range
|
300 - 950 V
|
||
|
Max.charge / discharge current
|
200 A / 100 A + 100 A
|
||
|
Number of battery ports
|
2
|
||
|
Max. charge / discharge current of each port
|
100 A
|
||
|
Communication
|
CAN / RS485
|
||
|
Output AC (Grid side)
|
|||
|
Rated output power
|
80 kW
|
100 kW
|
125 kW
|
|
Rated grid voltage
|
3/N/PE, 220 V / 380 V, 230 V / 400 V
|
||
|
Rated grid frequency
|
50 Hz / 60 Hz
|
||
|
Power factor
|
> 0.99 (0.8 leading - 0.8 lagging)
|
||
|
THDi
|
< 3%
|
||
|
Input AC (Grid side)
|
|||
|
Max. input current
|
250 A
|
||
|
Output AC (Back-up)
|
|||
|
Rated output power
|
80 kW
|
100 kW
|
125 kW
|
|
Back-up switch time
|
< 10 ms
|
||
|
Rated output voltage
|
3/N/PE, 220 V / 380 V, 230 V / 400 V
|
||
|
Rated frequency
|
50 Hz / 60 Hz
|
||
|
THDv (@linear load)
|
< 2%
|
||
|
Efficiency
|
|||
|
Max. efficiency
|
97.6%
|
||
|
Protection
|
|||
|
Anti-islanding protection
|
Yes
|
||
|
Output over current protection
|
Yes
|
||
|
Short circuit protection
|
Yes
|
||
|
Integrated DC switch
|
Yes
|
||
|
DC reverse-polarity protection
|
Yes
|
||
|
Surge protection
|
DC Type II / AC Type II
|
||
|
Integrated AFCI 2.0
|
Optional
|
||
|
Protection class / Over voltage category
|
I / II
|
||
|
General Data
|
|||
|
Max. allowable phase imbalance (grid & back-up)
|
100%
|
||
|
Max. power per phase (grid & back-up)
|
26.66 kW
|
33.33 kW
|
41.66 kW
|
|
Dimensions (W × H × D)
|
1174 × 814 × 400 mm
|
||
|
Weight
|
170 kg
|
||
|
Operating ambient temperature range
|
-25 ~ +60°C
|
||
|
Ingress protection
|
IP66
|
||
|
Cooling concept
|
Intelligent fan-cooling
|
||
|
Max. operation altitude
|
3000 m
|
||
|
Grid connection standard
|
G99, VDE-AR-N 4105/VDEV 0124, EN 50549-1&2/EN 50549-10, VDE 0126/UTE C 15/VFR:2019, NTS 631/
RD 1699/RD 244/UNE 206006/UNE 206007-1, CEI 0-21, C10/11, NRS 097-2-1, TOR, EIFS 2018.2,
IEC 62116, IEC 61727, IEC 60068, IEC 61683, EN 50530, MEA, PEA,PORTARIA Nº 140, DE 21 DE MARÇO DE 2022
|
||
|
standard
|
IEC/EN 62109-1/-2, IEC/EN 61000-6-2/-4, EN 55011
|
||






Q1: What makes the Solis 125kW inverter suitable for commercial applications?
A: Its 160% overload capacity (200ms) handles industrial motor startup currents, while dual battery ports and AI energy management optimize ROI for large-scale solar-plus-storage systems.
Q2: How does the monitoring system work?
A: The AI-powered platform enables real-time tracking via mobile/app, automatic tariff optimization, and VPP participation for revenue generation, supporting 4G/5G/Wi-Fi/Ethernet connectivity.
Q3: Does it support off-grid operation?
A: I Yes, with robust grid-forming capability and generator compatibility, it ensures stable off-grid power for critical industrial loads.
Q4: Can it integrate with generators?
A: Yes, it seamlessly integrates with generators (25-125kW range), enabling hybrid operation for backup power and reducing initial investment costs.
Q5: What's the warranty of this invereter
A:With 5 years standard warranty and 10 years extended warranty. During warranty period, any questions just contact us.