Customization: | Available |
---|---|
After-sales Service: | Yes |
Warranty: | Yes |
Still deciding? Get samples of US$ 9999/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Smart Monitoring System
Technical specifications
Technical Data
|
GW73/75/80/100/110/120/136KLV-HT
|
||||||
Input
|
|
||||||
Max. Input Voltage (V)
|
800
|
1100
|
|||||
MPPT Operating Voltage Range (V)
|
180 ~ 650
|
180 ~ 1000
|
|||||
Start-up Voltage (V)
|
200
|
||||||
Nominal Input Voltage (V)
|
370
|
600
|
750
|
||||
Max. Input Current per MPPT (A)
|
30
|
||||||
Max. Short Circuit Current per MPPT (A)
|
45
|
||||||
Number of MPP Trackers
|
12
|
10
|
12
|
12
|
12
|
||
Number of Strings per MPPT
|
2
|
||||||
Output
|
|||||||
Nominal Output Power (kW)
|
73
|
75
|
80
|
100*1
|
110
|
120
|
136
|
Nominal Output Apparent Power (kVA
|
73
|
75
|
80
|
100*1
|
110
|
120
|
136
|
Max. AC Active Power (kW)
|
69@208V;
73@220V;
75@240V
|
75
|
80
|
110*1*3
|
121*3
|
132*3
|
150*3
|
Max. AC Apparent Power (kVA)
|
75
|
75
|
88
|
110*1*4
|
121*4
|
132*4
|
150*4
|
Nominal Output Voltage (V)
|
220V, 3L / N / PE
or 3L / PE
|
380V / 400V, 3L / N / PE or 3L /
PE*2
|
400V, 3L / N / PE or 3L / PE*2
|
500V, 3L / PE
|
|||
Nominal AC Grid Frequency (Hz)
|
50 / 60
|
||||||
AC Grid Frequency Range (Hz)
|
45 ~ 55 / 55 ~ 65
|
||||||
Max. Output Current (A)
|
192.0
|
125.3
|
134.0
|
167.0
|
175.5
|
191.3
|
173.2
|
Power Factor
|
~1 (Adjustable from 0.8 leading to 0.8 lagging)
|
||||||
Max. Total Harmonic Distortion
|
<3%
|
||||||
Effciency
|
|||||||
Max. Efficiency
|
98.4%
|
98.6%
|
98.6%
|
98.6%
|
98.6%
|
98.6%
|
99.0%
|
European Efficiency
|
91.6%
|
98.3%
|
98.3%
|
98.3%
|
98.3%
|
98.3%
|
98.5%
|
Protection
|
|||||||
PV String Current Monitoring
|
Integrated
|
||||||
PV Insulation Resistance Detection
|
Integrated
|
||||||
Residual Current Monitoring
|
Integrated
|
||||||
PV Reverse Polarity Protection
|
Integrated
|
||||||
Anti-islanding Protection
|
Integrated
|
||||||
AC Overcurrent Protection
|
Integrated
|
||||||
AC Short Circuit Protection
|
Integrated
|
||||||
AC Overvoltage Protection
|
Integrated
|
||||||
DC Switch
|
Integrated
|
||||||
DC Surge Protection
|
Type II (Type I optional)
|
||||||
AC Surge Protection
|
Type II (Type I optional)
|
||||||
AFCI
|
Optional
|
||||||
Remote Shutdown
|
Optional
|
||||||
PID Recovery
|
Optional
|
||||||
General Data
|
|||||||
Operating Temperature Range (°C)
|
-30 ~ +60
|
||||||
Relative Humidity
|
0 ~ 100%
|
||||||
Max. Operating Altitude (m)
|
5000 (>4000 derating)
|
||||||
Cooling Method
|
Smart Fan Cooling
|
||||||
User Interface
|
LED, LCD (Optional), WLAN + APP
|
||||||
Communication Protocols
|
Modbus-RTU (SunSpec Compliant)
|
||||||
Weight (kg)
|
98.5
|
93.5
|
93.5
|
93.5
|
98.5
|
98.5
|
98.5
|
Dimension (W × H × D mm)
|
1008>678>343
|
||||||
Topology
|
Non-isolated
|
||||||
Self-consumption at Night (W)
|
<2
|
||||||
Ingress Protection Rating
|
IP66
|
||||||
DC Connector
|
MC4 (4 ~ 6mm²)
|
||||||
AC Connector
|
OT / DT terminal (Max. 300mm²)
|
Technical Data
|
GW225K-HT
|
GW250K-HT
|
GW225KN-HT
|
GW250KN-HT
|
Input
|
||||
Max. Input Voltage (V)
|
1500
|
1500
|
1500
|
1500
|
MPPT Operating Voltage Range (V)
|
500 ~ 1500
|
500 ~ 1500
|
500 ~ 1500
|
500 ~ 1500
|
Start-up Voltage (V)
|
550
|
550
|
550
|
550
|
Nominal Input Voltage (V)
|
1160
|
1160
|
1160
|
1160
|
Max. Input Current per MPPT (A)
|
30
|
30
|
60
|
60
|
Max. Short Circuit Current per MPPT (A)
|
50
|
50
|
90
|
90
|
Number of MPP Trackers
|
12
|
12
|
6
|
6
|
Number of Strings per MPPT
|
2
|
2
|
3
|
3
|
Output
|
||||
Nominal Output Power (kW)
|
225
|
250
|
225
|
250
|
Nominal Output Apparent Power (kVA)
|
225
|
250
|
225
|
250
|
Max. AC Active Power (kW)
|
247.5
|
250
|
247.5
|
250
|
Max. AC Apparent Power (kVA)
|
247.5
|
250
|
247.5
|
250
|
Nominal Output Voltage (V)
|
800, 3L / PE
|
800, 3L / PE
|
800, 3L / PE
|
800, 3L / PE
|
Nominal AC Grid Frequency (Hz)
|
50 / 60
|
50 / 60
|
50 / 60
|
50 / 60
|
Max. Output Current (A)
|
178.7
|
180.5
|
178.7
|
180.5
|
Power Factor
|
~1 (Adjustable from 0.8 leading to 0.8 lagging)
|
|||
Max. Total Harmonic Distortion
|
<3%
|
<3%
|
<3%
|
<3%
|
Effciency
|
||||
Max. Efficiency
|
99.0%
|
99.0%
|
99.0%
|
99.0%
|
European Efficiency
|
98.5%
|
98.5%
|
98.7%
|
98.7%
|
Protection
|
||||
PV String Current Monitoring
|
Integrated
|
Integrated
|
Integrated
|
Integrated
|
PV Insulation Resistance Detection
|
Integrated
|
Integrated
|
Integrated
|
Integrated
|
Residual Current Monitoring
|
Integrated
|
Integrated
|
Integrated
|
Integrated
|
PV Reverse Polarity Protection
|
Integrated
|
Integrated
|
Integrated
|
Integrated
|
Anti-islanding Protection
|
Integrated
|
Integrated
|
Integrated
|
Integrated
|
AC Overcurrent Protection
|
Integrated
|
Integrated
|
Integrated
|
Integrated
|
AC Short Circuit Protection
|
Integrated
|
Integrated
|
Integrated
|
Integrated
|
AC Overvoltage Protection
|
Integrated
|
Integrated
|
Integrated
|
Integrated
|
DC Switch
|
Integrated
|
Integrated
|
Integrated
|
Integrated
|
DC Surge Protection
|
Type II
|
Type II
|
Type II
|
Type II
|
AC Surge Protection
|
Type II
|
Type II
|
Type II
|
Type II
|
Emergency Power Off
|
Optional
|
Optional
|
Optional
|
Optional
|
Remote Shutdown
|
Optional
|
Optional
|
Optional
|
Optional
|
Anti-PID
|
Optional
|
Optional
|
Optional
|
Optional
|
General Data
|
||||
Operating Temperature Range (°C)
|
-30 ~ +60
|
-30 ~ +60
|
-30 ~ +60
|
-30 ~ +60
|
Relative Humidity
|
0 ~ 100%
|
0 ~ 100%
|
0 ~ 100%
|
0 ~ 100%
|
Max. Operating Altitude (m)
|
5000 (>4000 derating)
|
5000 (>4000 derating)
|
5000 (>4000 derating)
|
5000 (>4000 derating)
|
Cooling Method
|
Smart Fan Cooling
|
Smart Fan Cooling
|
Smart Fan Cooling
|
Smart Fan Cooling
|
User Interface
|
LED (LCD optional), Bluetooth + APP
|
|||
Communication
|
RS485 or PLC
|
RS485 or PLC
|
RS485 or PLC
|
RS485 or PLC
|
Communication Protocols
|
Modbus RTU
|
Modbus RTU
|
Modbus RTU
|
Modbus RTU
|
Weight (kg)
|
111
|
111
|
111
|
111
|
Dimension(W × H × D mm)
|
1091 × 678 × 341
|
1091 × 678 × 341
|
1091 × 678 × 341
|
1091 × 678 × 341
|
Topology
|
Non-isolated
|
Non-isolated
|
Non-isolated
|
Non-isolated
|
Self-consumption at Night (W)
|
<18
|
<18
|
<18
|
<18
|
Ingress Protection Rating
|
IP66
|
IP66
|
IP66
|
IP66
|
DC Connector
|
MC4-Evo2 (4 ~ 6mm²)
|
MC4-Evo2 (4 ~ 6mm²)
|
MC4-Evo2 (4 ~ 6mm²)
|
MC4-Evo2 (4 ~ 6mm²)
|
AC Connector
|
OT / DT terminal (Max. 300mm²)
|